York YP9C*C Manuel d'utilisateur Page 4

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 4
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 3
Subject to change without notice. Published in U.S.A. 538513- YTG-A-0809
Copyright © 2009 by Johnson Controls, Inc. All rights reserved. Supersedes: 410821-YTG-C-0409
Johnson Controls Unitary Products
5005 York Drive
Norman, OK 73069
All CFM’s are shown at 0.5” w.c. external static pressure.These units have variable speed motors that automatically adjust to provide constant CFM from 0.0”
to 0.6” w.c. static pressure. From 0.6” to 1.0” static pressure, CFM is reduced by 2% per 0.1” increase in static. Operation on duct systems with greater than
1.0” w.c. external static pressure is not recommended.
NOTE: At some settings, LOW COOL airflow may be lower that what is required to operate an airflow switch on certain models of electronic air cleaners. Con-
sult the instructions for the electronic air cleaner for further details.
Blower Performance CFM - Any Position
High / Low Speed Cooling CFM
060B12*C 080B12*C Jumper Settings
Hi Cool Lo Cool Hi Cool Lo Cool COOL Jumper ADJ Jumper
1305 850 1290 840 H B
1100 715 1090 710 MH B
1065 690 1015 660 H A
1000 650 1000 650 MH A
960 625 960 625 H C
760 495 760 495 ML B
900 585 900 585 MH C
660 430 660 430 L B
690 450 680 445 ML A
600 400 600 400 L A
620 400 620 400 ML C
550 400 540 400 L C
High / Low Speed Cooling CFM
080C16*C 100C16*C Jumper Settings
Hi Cool Lo Cool Hi Cool Lo Cool COOL Jumper ADJ Jumper
1670 1085 1655 1075 H B
1295 840 1275 820 MH B
1385 900 1345 875 H A
1175 765 1160 755 MH A
1245 810 1210 785 H C
995 645 1000 650 ML B
1055 685 1045 680 MH C
935 605 955 620 L B
905 590 910 590 ML A
850 550 870 565 L A
815 530 815 530 ML C
765 500 785 510 L C
High / Low Speed Cooling CFM
100C20*C 120D20*C Jumper Settings
Hi Cool Lo Cool Hi Cool Lo Cool COOL Jumper ADJ Jumper
2215 1440 2180 1415 H B
1765 1145 1760 1140 MH B
1820 1180 1800 1170 H A
1605 1040 1595 1035 MH A
1635 1060 1620 1050 H C
1270 825 1255 815 ML B
1445 940 1435 935 MH C
1055 685 1050 680 L B
1155 750 1160 755 ML A
960 620 960 615 L A
1040 675 1035 670 ML C
860 560 840 545 L C
Vue de la page 3