INSTALLATION
INSTRUCTIONS
CAUTION: READ ALL SAFETY GUIDES
BEFORE YOU START TO INSTALL
YOUR FURNACE.
SAVE THIS MANUAL
ALL POSITION
AUTOMATIC IGNITION FURNACES
G8C / FG8 SERIES MODELS
50 - 125 MBH INPUT
UPFLOW / HORIZONTAL
AUTOMATIC IGNITION FURNACES
G8C / FG8 SERIES MODELS
150 MBH INPUT
035-15241-003 Rev. A (201)
TABLE OF CONTENTS
GENERAL INFORMATION . . . . . . . . . . . . . . . . . . . . . . . 2
FURNACE SPECIFICATIONS . . . . . . . . . . . . . . . . . . . . 3
PRE-INSTALLATION INSPECTION . . . . . . . . . . . . . . . . 4
CODE COMPLIANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
INSTALLATION POSITION
(50-125 MBH Models) . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
INSTALLATION POSITION
(150 MBH Models) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
CONVERSION INFORMATION
(50-125 MBH Models) . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
TO CONVERT FROM DOWNFLOW TO UPFLOW
CONFIGURATION (50-125 MBH Models) . . . . . . . . . . . 4
TO CONVERT FROM UPFLOW TO DOWNFLOW
CONFIGURATION (50-125 MBH Models) . . . . . . . . . . . 5
FURNACE LOCATION . . . . . . . . . . . . . . . . . . . . . . . . . . 6
COMBUSTION AND VENTILATION AIR . . . . . . . . . . . . 7
FURNACE SIZING AND DUCT
SYSTEM DESIGN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
RETURN AIR AND FILTERS . . . . . . . . . . . . . . . . . . . . . 9
GAS PIPING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
VENTING (CATEGORY I) . . . . . . . . . . . . . . . . . . . . . . . 13
SIDEWALL VENTING . . . . . . . . . . . . . . . . . . . . . . . . . . 15
ELECTRICAL WIRING . . . . . . . . . . . . . . . . . . . . . . . . . 15
WIRING DIAGRAM . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
PRE-OPERATIONAL CHECKS . . . . . . . . . . . . . . . . . . 19
SEQUENCE OF OPERATION . . . . . . . . . . . . . . . . . . . 19
FURNACE OPERATION . . . . . . . . . . . . . . . . . . . . . . . . 20
INSTALLATION CHECKS . . . . . . . . . . . . . . . . . . . . . . 21
SERVICE INSTRUCTIONS . . . . . . . . . . . . . . . . . . . . . . 22
REPLACEMENT PARTS . . . . . . . . . . . . . . . . . . . . . . . 22
EFFICIENCY
RATING
CERTIFIED
Vue de la page 0
1 2 3 4 5 6 ... 23 24

Résumé du contenu

Page 1 - INSTRUCTIONS

INSTALLATION INSTRUCTIONSCAUTION: READ ALL SAFETY GUIDES BEFORE YOU START TO INSTALL YOUR FURNACE.SAVE THIS MANUALALL POSITION AUTOMATIC IGNITION FURN

Page 2 - GENERAL INFORMATION

035-15241-003 Rev. A (201)10 Unitary Products GroupDOWNFLOW (50-125 MBH MODELS ONLY)Filters must be mounted in a location where they are easilyaccessi

Page 3 - FURNACE SPECIFICATIONS

035-15241-003 Rev. A (201)Unitary Products Group 11 FIGURE 9: DOWNFLOW CONFIGURATION (50-125 MBH MODELS ONLY)BLOWERDOORSWITCHROLL-OUTSWITCHESBURNERSH

Page 4

035-15241-003 Rev. A (201)12 Unitary Products GroupUnless prohibited by local codes, it is permissible to use aflexible corrugated metal gas connector

Page 5 - (50-125 MBH Models)

035-15241-003 Rev. A (201)Unitary Products Group 13VENTING (CATEGORY I)This furnace is a fan-assisted Category I furnace which oper-ates with a non-po

Page 6 - FURNACE LOCATION

035-15241-003 Rev. A (201)14 Unitary Products GroupINSPECTION OF EXISTING CHIMNEY1. Before connecting the vent connector to a chimney, the chimney pas

Page 7 - (50-125 MBH MODELS)

035-15241-003 Rev. A (201)Unitary Products Group 153. Insofar, as is practical, close all building doors and win-dows and all doors between the space

Page 8 - FIGURE 6: AIR OPENINGS

035-15241-003 Rev. A (201)16 Unitary Products GroupACCESSORIESA humidifier or electronic air cleaner may be used with thisfurnace. All accessories sho

Page 9 - RETURN AIR AND FILTERS

035-15241-003 Rev. A (201)Unitary Products Group 17BLOWER PERFORMANCEUPFLOW, SINGLE SIDE RETURN APPLICATIONSAirflow is expressed in standard cubic fee

Page 10 - GAS PIPING

035-15241-003 Rev. A (201)18 Unitary Products GroupBLOWER TIMINGSThe electronic furnace control supplied on this furnace con-trols the blower delay ti

Page 11 - Unitary Products Group 11

035-15241-003 Rev. A (201)Unitary Products Group 19WIRING DIAGRAMPRE-OPERATIONAL CHECKS1. Be sure that the furnace is equipped for the type of gas bei

Page 12

035-15241-003 Rev. A (201)2 Unitary Products GroupIMPROPER INSTALLATION MAY CREATE A CONDITION WHERE THE OPERATION OF THE PRODUCT COULD CAUSE PERSONAL

Page 13 - VENTING (CATEGORY I)

035-15241-003 Rev. A (201)20 Unitary Products Group6. If the burners fail to light within 6-8 seconds after the gas valve opens, the gas valve will cl

Page 14

035-15241-003 Rev. A (201)Unitary Products Group 21INSTALLATION CHECKSCHECKING GAS INPUT RATEThe maximum BTUH input capacity for each model is shownon

Page 15 - ELECTRICAL WIRING

035-15241-003 Rev. A (201)22 Unitary Products Group2. Place thermometer in return air duct about two feet from furnace, with the tip of the thermomete

Page 16 - ACCESSORIES

035-15241-003 Rev. A (201)Unitary Products Group 231. Door Panel2. Blower Door3. Heat Exchanger4. Vent Blower5. Limit Switch6. Rollout Switch7. Top Sh

Page 17 - BLOWER PERFORMANCE

Subject to change without notice. Printed in U.S.A. 035-15241-003 Rev. A (201)Copyright © by York International Corp. 2001. All rights reserved. Super

Page 18 - TIME (90 SECONDS SHOWN)

035-15241-003 Rev. A (201)Unitary Products Group 3FURNACE SPECIFICATIONS * All models are supplied with 3” vent connections. An installer supplied tra

Page 19 - SEQUENCE OF OPERATION

035-15241-003 Rev. A (201)4 Unitary Products GroupPRE-INSTALLATION INSPECTIONInspect the shipping container and furnace for any evidenceof shipping da

Page 20 - FURNACE OPERATION

035-15241-003 Rev. A (201)Unitary Products Group 5.TO CONVERT FROM UPFLOW TO DOWNFLOW CONFIGURATION(50-125 MBH Models)1. Lay the furnace on its back.2

Page 21 - INSTALLATION CHECKS

035-15241-003 Rev. A (201)6 Unitary Products Group16. Install the top cap at the opposite end of furnace from the vent blower, using the seven sheet m

Page 22 - REPLACEMENT PARTS

035-15241-003 Rev. A (201)Unitary Products Group 7INSTALLATIONS ON COMBUSTIBLE FLOORING (50-125 MBH MODELS)This furnace may not be installed directly

Page 23

035-15241-003 Rev. A (201)8 Unitary Products GroupFURNACE SIZING AND DUCT SYSTEM DESIGNThe duct system must be installed in conformance withASHRAE/NFP

Page 24 - SERVICE RECORDS

035-15241-003 Rev. A (201)Unitary Products Group 92. If two duct systems are used as could be the case with a coil-blower or a self-contained A/C unit