INSTALLATION
MANUAL
CAUTION: READ ALL SAFETY GUIDES BEFORE YOU
BEGIN TO INSTALL YOUR UNIT.
SAVE THIS MANUAL
SUNLINE™
GAS/ELECTRIC SINGLE PACKAGE
AIR CONDITIONERS
D(CE, CG) 036, 048, 060 & 072
D(HE, HG) 036, 048 & 060
177817-YIM-A-0506
CONTENTS
GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
SAFETY CONSIDERATIONS. . . . . . . . . . . . . . . . . 5
INSPECTION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
REFERENCE. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
RENEWAL PARTS . . . . . . . . . . . . . . . . . . . . . . . . . 6
APPROVALS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
PRODUCT NOMENCLATURE . . . . . . . . . . . . . . . . 6
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
START-UP (COOLING) . . . . . . . . . . . . . . . . . . . . 45
START-UP (GAS HEAT). . . . . . . . . . . . . . . . . . . . 45
TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . 48
SEE THE FOLLOWING PAGES FOR A COMPLETE TABLE OF CONTENTS.
NOTES, CAUTIONS AND WARNINGS
The installer should pay particular attention to the words:
NOTE, CAUTION, and WARNING. Notes
are intended to
clarify or make the installation easier. Cautions
are given to
prevent equipment damage. Warnings
are given to alert
installer that personal injury and/or equipment damage may
result if installation procedure is not handled properly.
Vue de la page 0
1 2 3 4 5 6 ... 55 56

Résumé du contenu

Page 1 - INSTALLATION

INSTALLATION MANUALCAUTION: READ ALL SAFETY GUIDES BEFORE YOU BEGIN TO INSTALL YOUR UNIT.SAVE THIS MANUALSUNLINE™GAS/ELECTRIC SINGLE PACKAGEAIR CONDIT

Page 2 - TABLE OF CONTENTS

177817-YIM-A-050610 Unitary Products GroupSections 7.2, 7.3 or 7.4 of Gas Installation Codes CSA-B149.1 (in Canada) and/or applicable provisions of th

Page 3 - LIST OF FIGURES

177817-YIM-A-0506Unitary Products Group 11FILTERSOne-inch or two-inch filters can be supplied with eachunit. Filters must always be installed ahead of

Page 4 - LIST OF TABLES

177817-YIM-A-050612 Unitary Products GroupTYPICAL POWER WIRINGTYPICAL CONTROL WIRINGFIGURE 3 - TYPICAL FIELD POWER & CONTROL WIRINGREFER TO THE EL

Page 5 - INSPECTION

177817-YIM-A-0506Unitary Products Group 13THERMOSTATThe room thermostat should be located on an insidewall approximately 56 inches above the floor whe

Page 6 - PRODUCT NOMENCLATURE

177817-YIM-A-050614 Unitary Products GroupGAS HEATThese gas-fired heaters have aluminized-steel tubularheat exchangers with spark ignition with proven

Page 7 - Unitary Products Group 7

177817-YIM-A-0506Unitary Products Group 15GAS PIPINGProper sizing of gas piping depends on the cubic feetper hour of gas flow required, specific gravi

Page 8

177817-YIM-A-050616 Unitary Products Group6. The furnace and its individual manual shut-offvalve must be disconnected from the gas supplypiping system

Page 9 - Unitary Products Group 9

177817-YIM-A-0506Unitary Products Group 17L.P./propane gas is an excellent solvent and specialpipe compound must be used when assembling pipingfor thi

Page 10 - 10 Unitary Products Group

177817-YIM-A-050618 Unitary Products GroupPower exhaust is only available as a field installedaccessory.ECONOMIZER AND POWER EXHAUST DAMPER SET POINT

Page 11 - Unitary Products Group 11

177817-YIM-A-0506Unitary Products Group 19FIGURE 7 - ENTHALPY SETPOINT ADJUSTMENT40(4)70(21)50(10)55(13)60(16)65(18)35(2)45(7)75(24)80(27)35(2)40(4)45

Page 12 - SINGLE STAGE

177817-YIM-A-05062 Unitary Products GroupTABLE OF CONTENTSGENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5SAFETY

Page 13 - 18 AWG 150 Feet

177817-YIM-A-050620 Unitary Products Group FIGURE 9 - FOUR AND SIX POINT LOADINGTABLE 6: CENTER OF GRAVITY (ALL MODELS)DIMENSION 3 - 5 TON 6 TONX 40-¾

Page 14 - 14 Unitary Products Group

177817-YIM-A-0506Unitary Products Group 21TABLE 9: D(CE, CG) PHYSICAL DATAMODELSD(CE, CG)036 048 060 072EVAPORATORBLOWERCentrifugal Blower (Dia. x Wd.

Page 15 - GAS CONNECTION

177817-YIM-A-050622 Unitary Products GroupTABLE 11: D(HE, HG) PHYSICAL DATAMODELSD(HE, HG)036 048 060EVAPORATORBLOWERCentrifugal Blower (Dia. x Wd. in

Page 16 - L.P. UNITS, TANKS AND PIPING

177817-YIM-A-0506Unitary Products Group 23TABLE 13: ELECTRICAL DATA - D(CE, CG) 036-072 DIRECT DRIVEMODELTONNAGEVOLTAGECOMPRESSORSOD FANMOTORFLAIDBLOW

Page 17 - VENT AND COMBUSTION AIR HOODS

177817-YIM-A-050624 Unitary Products GroupMODELTONNAGEVOLTAGECOMPRESSORSOD FANMOTORFLAIDBLOWERMOTORFLAELECTRIC HEATERMODEL NO.HEATERKWHEATERAMPSMIN.CI

Page 18

177817-YIM-A-0506Unitary Products Group 25TABLE 14: ELECTRICAL DATA - D(CE, CG) 036-072 BELT DRIVEMODELTONNAGEVOLTAGECOMPRESSORSOD FANMOTORFLAIDBLOWER

Page 19 - Unitary Products Group 19

177817-YIM-A-050626 Unitary Products GroupMODELTONNAGEVOLTAGECOMPRESSORSOD FANMOTORFLAIDBLOWERMOTORFLAELECTRIC HEATERMODEL NO.HEATER KW HEATER AMPSMIN

Page 20 - 20 Unitary Products Group

177817-YIM-A-0506Unitary Products Group 27TABLE 15: ELECTRICAL DATA - D(HE, HG) 036-060 BELT DRIVEMODELTONNAGEVOLTAGECOMPRESSORSOD FANMOTORFLAIDBLOWER

Page 21 - Unitary Products Group 21

177817-YIM-A-050628 Unitary Products GroupMODELTONNAGEVOLTAGECOMPRESSORSOD FANMOTORFLAIDBLOWERMOTORFLAELECTRIC HEATERMODEL NO.HEATERKWHEATERAMPSMIN.CI

Page 22 - 22 Unitary Products Group

177817-YIM-A-0506Unitary Products Group 29TABLE 16: ELECTRIC HEAT CORRECTION FACTORSNOMINAL VOLTAGE VOLTAGE kW CAP. MULTIPLIER208208 0.75240230 0.924

Page 23 - Unitary Products Group 23

177817-YIM-A-0506Unitary Products Group 3LIST OF FIGURESFig. # Pg. #1 RECOMMENDED DRAIN PIPING . . . . . . . . . . . . . . 102 COMPRESSOR RESTRAINING

Page 24 - 24 Unitary Products Group

177817-YIM-A-050630 Unitary Products GroupFIGURE 11 - UNIT DIMENSIONS (3 - 6 TON COOLING/GAS HEAT) FRONT VIEWFIGURE 12 - UNIT WITH ECONOMIZER RAINHOO

Page 25 - Unitary Products Group 25

177817-YIM-A-0506Unitary Products Group 31FIGURE 13 - UNIT WITH FIXED OUTDOOR AIR/MOTORIZED DAMPER RAINHOODDETAIL “B”FIGURE 14 - UNIT DIMENSIONS (REAR

Page 26 - 26 Unitary Products Group

177817-YIM-A-050632 Unitary Products GroupFIGURE 15 - DISCONNECT/BLOWER ACCESS LOCATIONDISCONNECT SWITCH LOCATIONAND MOTOR ACCESS PANEL FORUNIT WITH “

Page 27 - Unitary Products Group 27

177817-YIM-A-0506Unitary Products Group 33 TABLE 20: SUPPLY AIR BLOWER PERFORMANCE (3 TON BELT DRIVE) - SIDE DUCT APPLICATIONRPM WATTS RPM WATTS RPM W

Page 28 - 28 Unitary Products Group

177817-YIM-A-050634 Unitary Products Group TABLE 21: SUPPLY AIR BLOWER PERFORMANCE (4 TON BELT DRIVE) - SIDE DUCT APPLICATIONRPM WATTS RPM WATTS RPM

Page 29 - TABLE 17: VOLTAGE LIMITATIONS

177817-YIM-A-0506Unitary Products Group 35 TABLE 22: SUPPLY AIR BLOWER PERFORMANCE (5 TON BELT DRIVE) - SIDE DUCT APPLICATIONRPM WATTS RPM WATTS RPM W

Page 30 - DETAIL “A”

177817-YIM-A-050636 Unitary Products Group TABLE 23: SUPPLY AIR BLOWER PERFORMANCE (6 TON BELT DRIVE) - SIDE DUCT APPLICATIONRPM WATTS RPM WATTS RPM W

Page 31 - DETAIL “B”

177817-YIM-A-0506Unitary Products Group 37 TABLE 24: SUPPLY AIR BLOWER PERFORMANCE (3 - 6 TON DIRECT DRIVE) - SIDE DUCT APPLICATIONCFM WATTS CFM WAT

Page 32 - TABLE 19: MINIMUM CLEARANCES

177817-YIM-A-050638 Unitary Products GroupPHASINGCheck for proper compressor rotation. If the blower orcompressors rotate in the wrong direction at st

Page 33 - Unitary Products Group 33

177817-YIM-A-0506Unitary Products Group 39Start the supply air blower motor. Adjust the resis-tances in both the supply and the return air duct sys-te

Page 34 - 34 Unitary Products Group

177817-YIM-A-05064 Unitary Products GroupLIST OF TABLESTbl. # Pg. #1 UNIT APPLICATION DATA (D(CE, CG),D(HE, HG)) . . . . . . . . . . . . . . . . . .

Page 35 - Unitary Products Group 35

177817-YIM-A-050640 Unitary Products GroupCOOLING SEQUENCE OF OPERATIONCONTINUOUS BLOWERBy setting the room thermostat fan switch to “ON,” thesupply a

Page 36 - 36 Unitary Products Group

177817-YIM-A-0506Unitary Products Group 41HIGH-PRESSURE LIMIT SWITCHDuring cooling operation, if a high-pressure limit switchopens, the UCB will de-en

Page 37 - Unitary Products Group 37

177817-YIM-A-050642 Unitary Products Groupsor, the protector will open to shut down the compres-sor. The UCB incorporates features to minimizecompress

Page 38 - 38 Unitary Products Group

177817-YIM-A-0506Unitary Products Group 43a greater temperature swing in the conditioned space.Reducing the value below the correct setpoint will give

Page 39 - OPERATION

177817-YIM-A-050644 Unitary Products Groupiary limit is of the manual reset type and is mounted inthe upper right hand corner of the panel between the

Page 40

177817-YIM-A-0506Unitary Products Group 45HEAT ANTICIPATOR SETPOINTSIt is important that the anticipator setpoint be correct.Too high of a setting wil

Page 41

177817-YIM-A-050646 Unitary Products Group2. Turn room thermostat to lowest setting.3. Turn gas valve knob or switch to “on” position.4. Turn “on” ele

Page 42

177817-YIM-A-0506Unitary Products Group 47MANIFOLD GAS PRESSURE ADJUSTMENTAdjustments to gas flow may be made by turning thepressure regulator adjusti

Page 43 - TEMPERATURE LIMITS

177817-YIM-A-050648 Unitary Products GroupNOTE: To find the Btu input, multiply the number ofcubic feet of gas consumed per hour by theBtu content of

Page 44

177817-YIM-A-0506Unitary Products Group 492. If the blower motor runs with the fan switch in theON position but will not run after the compressorhas e

Page 45 - START-UP (GAS HEAT)

177817-YIM-A-0506Unitary Products Group 5GENERALYORK Model D(CE, CG) and D(HE, HG) units areeither single package cooling units or single packagegas-f

Page 46 - TO SHUT DOWN:

177817-YIM-A-050650 Unitary Products GroupCheck for 24 volts at the HPS1, LPS1, and FS1terminals of the UCB. If a switch has opened, thereshould be a

Page 47 - NATURAL GAS

177817-YIM-A-0506Unitary Products Group 51Before beginning symptomatic troubleshooting activi-ties read the flash code LEDs on the unit control board(

Page 48 - TROUBLESHOOTING

177817-YIM-A-050652 Unitary Products Groupwheel area for debris. If debris is present, then cleardebris and verify proper furnace operation. If clear,

Page 49

177817-YIM-A-0506Unitary Products Group 53then set the gas valve to the off position and tempo-rarily apply control voltage (~24 volts) to pin 9 of th

Page 50 - 50 Unitary Products Group

177817-YIM-A-050654 Unitary Products Grouproom thermostat. If 24 volts is not present from theroom thermostat, check for the following:a. Proper opera

Page 51

177817-YIM-A-0506Unitary Products Group 554. Make sure that the ground connections at the pilotburner, gas valve and ignition control are intact.Check

Page 52

177817-YIM-A-0506Subject to change without notice. Printed in U.S.A. Supersedes: 65716/530.18-N8Y, 66225/530.18-N7YCopyright © 2006 by Unitary Produ

Page 53 - UNEXPECTED FLAME PRESENCE

177817-YIM-A-05066 Unitary Products GroupREFERENCEAdditional information is available in the following refer-ence forms:• Technical Guide - D(CE, CG)

Page 54

177817-YIM-A-0506Unitary Products Group 7D 8 C G 4NPRODUCT GENERATION3 = 3rd Generation8 = 8th GenerationPRODUCT CATEGORYD = Single Package Air Condit

Page 55 - Unitary Products Group 55

177817-YIM-A-05068 Unitary Products GroupINSTALLATIONINSTALLATION SAFETY INFORMATION:Read these instructions before continuing this appli-ance install

Page 56 - Group Drive 73069

177817-YIM-A-0506Unitary Products Group 9LOCATIONUse the following guidelines to select a suitable loca-tion for these units.1. Unit is designed for o