York R-410A Manuel d'utilisateur Page 42

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 206
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 41
528150-YTG-G-1210
42 Johnson Controls Unitary Products
115°F 125°F
1625
77 78.3 7.0 31.2 26.7 19.5 - - - 69.4 7.5 24.9 23.7 17.5 - - -
72 70.7 6.8 44.7 37.4 30.1 22.9 - - 63.1 7.3 40.9 34.3 27.8 21.3 - -
67 63.2 6.7 58.1 48.0 40.8 33.5 26.2 - 56.8 7.1 56.8 44.7 38.1 31.6 25.1 -
62 55.8 6.5 55.8 55.8 51.1 43.9 36.6 29.3 48.6 6.9 48.6 48.6 48.6 41.9 35.4 28.9
1950
77 80.3 7.0 37.9 29.7 21.4 - - - 71.3 7.6 36.4 27.6 19.3 - - -
72 72.5 6.9 49.6 41.4 33.2 24.9 - - 64.8 7.4 47.3 39.0 30.7 22.3 - -
67 64.7 6.7 61.4 53.1 44.9 36.7 28.5 - 58.3 7.2 58.3 50.4 42.1 33.7 25.4 -
62 57.2 6.6 57.2 57.2 56.3 48.1 39.9 31.6 49.9 6.9 49.9 49.9 49.9 45.1 36.8 28.5
57 61.4 6.6 61.4 61.3 53.1 44.9 36.7 28.4 55.7 7.1 55.7 55.7 48.0 39.7 31.4 23.1
2275
77 82.2 7.1 44.6 32.6 23.4 - - - 73.1 7.6 47.8 31.5 21.1 - - -
72 74.2 6.9 54.6 45.4 36.2 27.0 - - 66.4 7.4 53.8 43.6 33.5 23.4 - -
67 66.3 6.8 64.6 58.2 49.1 39.9 30.7 - 59.7 7.3 59.7 56.1 46.0 35.9 25.7 -
62 58.6 6.6 58.6 58.6 61.5 52.3 43.1 34.0 51.2 7.0 51.2 51.2 51.2 48.3 38.2 28.0
57 62.9 6.7 62.9 62.9 58.0 48.8 39.6 30.5 57.1 7.1 57.1 57.1 52.5 42.4 32.3 22.1
2600
77 84.1 7.1 51.3 35.5 25.4 - - - 74.9 7.7 59.3 35.4 22.9 - - -
72 76.0 7.0 59.6 49.4 39.3 29.1 - - 68.1 7.5 60.2 48.3 36.4 24.5 - -
67 67.9 6.8 67.9 63.3 53.2 43.1 32.9 - 61.2 7.3 61.2 61.2 49.9 38.0 26.0 -
62 60.0 6.6 60.0 60.0 66.7 56.6 46.4 36.3 52.4 7.1 52.4 52.4 52.4 51.5 39.6 27.6
57 64.4 6.7 64.4 64.4 62.9 52.8 42.6 32.5 58.5 7.2 58.5 58.5 57.0 45.1 33.1 21.2
2925
72 77.4 7.0 64.4 53.3 42.1 31.0 - - 68.5 7.5 63.2 51.2 39.2 27.2 - -
67 69.1 6.8 69.1 66.8 57.0 45.9 34.8 - 61.6 7.3 61.6 61.6 53.7 41.7 29.7 -
62 61.1 6.7 61.1 61.1 64.4 53.3 42.2 31.0 52.7 7.1 52.7 52.7 52.7 46.2 34.2 22.1
57 65.6 6.7 65.6 65.6 64.8 53.7 42.5 31.4 58.9 7.2 58.9 58.9 58.2 46.1 34.1 22.1
3250
72 78.8 7.0 69.2 57.1 45.0 32.9 - - 68.9 7.6 66.2 54.1 42.0 29.9 - -
67 70.3 6.9 70.3 70.3 60.9 48.8 36.6 - 62.0 7.4 62.0 62.0 57.6 45.5 33.3 -
62 62.2 6.7 62.2 62.2 62.2 50.0 37.9 25.8 53.0 7.1 53.0 53.0 53.0 40.9 28.8 16.7
57 66.7 6.8 66.7 66.7 66.7 54.6 42.5 30.3 59.3 7.2 59.3 59.3 59.3 47.2 35.1 23.0
1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
ZH078 (6.5 Ton) (Continued)
Air on
Evaporator Coil
Temperature of Air on Condenser Coil
Total
Capacity
1
(MBh)
Total
Input
(kW)
2
Sensible Capacity (MBh)
Total
Capacity
1
(MBh)
Total
Input
(kW)
2
Sensible Capacity (MBh)
CFM
WB
(°F)
Return Dry Bulb (°F) Return Dry Bulb (°F)
90 85 80 75 70 65 90 85 80 75 70 65