FORM 201.23-EG1 (1007)Air Cooled Screw Liquid Chillers150 - 385 TONS(527 - 1354 kWi)2 and 3 Compressor50 and 60 HzASHRAE 90.1 CompliantR134a�140-200
JOHNSON CONTROLS10Temperatures and FlowsTEMPERATURE AND FLOWS(English Units)NOTES: 1. For leaving brine temperature below 40°F (4.4°C), contact your
JOHNSON CONTROLS100Dimensions – SI - continuedNotes:1. Placement on a level surface free of obstructions (including snow, for winter operation) or air
JOHNSON CONTROLSFORM 201.23-EG1 (1007)101POWER: SINGLE POINT WITH TERMINAL BLOCK12781270193025151882135623133 (TYP)1754626382387DDXGCZXGCYCONTROL PANE
JOHNSON CONTROLS102Dimensions – SI - continuedNotes:1. Placement on a level surface free of obstructions (including snow, for winter operation) or air
JOHNSON CONTROLSFORM 201.23-EG1 (1007)1032387175CONTROL PANELORIGIN13562311278127019302863483POWER: SINGLE POINT WITH TERMINAL BLOCKVIEW D-D16 MOUNTIN
JOHNSON CONTROLS104Isolator Locations – EnglishCONTROL PANELL1L2R6R1L6L5L4L3R2R3R4R5R7L7xySTANDARD EFFICIENCY - ENGLISHMODEL Isolator Locations ( x ,
JOHNSON CONTROLSFORM 201.23-EG1 (1007)105MODEL Isolator Locations ( x , y ) - in. and Point Loads - lbs60 Hz 50 Hz 1 2 3 4 5 6 7YCIV0267S/P YCIV1000S/
JOHNSON CONTROLS106Isolator Locations – English – continuedCONTROL PANELL1L2R6R1L6L5L4L3R2R3R4R5R7L7xyHIGH EFFICIENCY - ENGLISHMODEL Isolator Location
JOHNSON CONTROLSFORM 201.23-EG1 (1007)107MODEL Isolator Locations ( x , y ) - in. and Point Loads - lbs60 Hz 50 Hz 1 2 3 4 5 6 7YCIV0227E/V YCIV0830E/
JOHNSON CONTROLS108CONTROL PANELL1L2R6R1L6L5L4L3R2R3R4R5R7L7xyIsolator Locations – SISTANDARD EFFICIENCY - SIMODEL Isolator Locations ( x , y ) - mm a
JOHNSON CONTROLSFORM 201.23-EG1 (1007)109MODEL Isolator Locations ( x , y ) - mm and Point Loads - kg60 Hz 50 Hz 1 2 3 4 5 6 7YCIV0247S/P YCIV0920S/PL
JOHNSON CONTROLSFORM 201.23-EG1 (1007)11TEMPERATURE AND FLOWS(SI Units)NOTES: 1. For leaving brine temperature below 4.4°C, contact your nearest John
JOHNSON CONTROLS110CONTROL PANELL1L2R6R1L6L5L4L3R2R3R4R5R7L7xyIsolator Locations – SI – continuedHIGH EFFICIENCY - SIMODELIsolator Locations ( x , y )
JOHNSON CONTROLSFORM 201.23-EG1 (1007)111MODELIsolator Locations ( x , y ) - mm and Point Loads - kg60 Hz 50 Hz1 2 3 4 5 6 7YCIV0227E/V YCIV0830E/VLEF
JOHNSON CONTROLS112FOR UNITS WITH ALL POINT LOADS LESS THATN 1404 LBS (637 KG)Weight Range (lbs) Weight Range (kg) Model Number Color239 to 384 lbs 10
JOHNSON CONTROLSFORM 201.23-EG1 (1007)113Weight Range (lbs)Weight Range (kg)Model Number ColorUp to 751 lbs Up to 341 kg ND-C Yellow751 to 1651 lbs 34
JOHNSON CONTROLS114Isolator Details (cont'd)ENGLISHSIZE H T D E L HCL W HCW MBD2-C2 8 1/2 3/8 5/8 1 3/8 14 12 1/4 5 1/4 3 1/ 2 5
JOHNSON CONTROLSFORM 201.23-EG1 (1007)115INTENTIONALLY LEFT BLANK
JOHNSON CONTROLS116Electrical Data - 2 Comp Standard EfciencySee page 192 for Electrical Data footnotes.Standard Efciency YCIV_ _ _ _ S/P Standard
JOHNSON CONTROLSFORM 201.23-EG1 (1007)117Standard Efciency YCIV_ _ _ _ S/P Standard Efciency YCIV_ _ _ _ S/PModel No./NameplateSystem 1 System 2
JOHNSON CONTROLS118Electrical Data - 2 Comp High EfciencyHigh Efciency YCIV_ _ _ _ E/V High Efciency YCIV_ _ _ _ E/VModel No./NameplateSystem 1
JOHNSON CONTROLSFORM 201.23-EG1 (1007)119High Efciency YCIV_ _ _ _ E/V High Efciency YCIV_ _ _ _ E/VModel No./NameplateSystem 1 System 2Std. &am
JOHNSON CONTROLS12Water Pressure DropENGLISH UNITSCOOLERMODEL NUMBER YCIV60Hz 50HzA 0157(S/P) 0600(S/P)B0157(E/V) 0590(E/V)0177(S/P/E/V) 0630(E/V), 06
JOHNSON CONTROLS120Electrical Data - 3 Comp Standard EfciencySee page 192 for Electrical Data footnotes.Model No./NameplateSystem 1 System 2 System 2
JOHNSON CONTROLSFORM 201.23-EG1 (1007)121Model No./NameplateSystem 1 System 2 System 2 System 3Std. & Ultra Quiet Cond. Fans High Head/Static Cond
JOHNSON CONTROLS122Electrical Data - 3 Comp High EfciencySee page 192 for Electrical Data footnotes.Model No./NameplateSystem 1 System 2 System 2 Sys
JOHNSON CONTROLSFORM 201.23-EG1 (1007)123Model No./NameplateSystem 1 System 2 System 2 System 3Std. & Ultra Quiet Cond. Fans High Head/Static Cond
JOHNSON CONTROLS124 LEGEND C.B. CIRCUIT BREAKER D.E. DUAL ELEMENT FUSE DISC SW DISCONNECT SWITCH FACT CB FACTORY-MOUNTED CIRCUIT BREAKER FLA
JOHNSON CONTROLSFORM 201.23-EG1 (1007)125FIG. 1 – TWO COMPRESSOR WIRING DIAGRAM WITH CIRCUIT BREAKER2 COMPRESSOR POWER WIRING CONNECTIONSFIG. 2 – TWO
JOHNSON CONTROLS126Power Wiring – continuedFIG. 3 – THREE COMPRESSOR WIRING DIAGRAM WITH CIRCUIT BREAKER – SINGLE POINTFIG. 4 – THREE COMPRESSOR WIRI
JOHNSON CONTROLSFORM 201.23-EG1 (1007)127INTENTIONALLY LEFT BLANK
JOHNSON CONTROLS128Typical Control Wiring - Two Compressor
JOHNSON CONTROLSFORM 201.23-EG1 (1007)129For informational purposes only. Do not attempt to tie into wiring without a proper wiring diagram.
JOHNSON CONTROLSFORM 201.23-EG1 (1007)13SI UNITS
JOHNSON CONTROLS130Typical Control Wiring - Three Compressor
JOHNSON CONTROLSFORM 201.23-EG1 (1007)131For informational purposes only. Do not attempt to tie into wiring without a proper wiring diagram.
JOHNSON CONTROLS132UNIT LOCATIONThe YCIV chillers are designed for outdoor installation. When selecting a site for installation, be guided by the fol
JOHNSON CONTROLSFORM 201.23-EG1 (1007)133Guide SpecicationsPART 1 — GENERAL1.01 SCOPEA. The requirements of the General Conditions, Supple-mentary Co
JOHNSON CONTROLS134Guide Specications – continuedsystem, interconnecting wiring, safety and operating controls including capacity controller, control
JOHNSON CONTROLSFORM 201.23-EG1 (1007)135with full height collars. Subcooling coil an integral part of condenser. Design working pressure s
JOHNSON CONTROLS136atures, ambient, lead compressor identication, clock and schedule, (variable) out of range, remote input indication, chilled liqui
JOHNSON CONTROLSFORM 201.23-EG1 (1007)137components.4. Louvered/Wire Panels: Louvered steel panels on external condenser coil faces, painted to match
JOHNSON CONTROLS138
JOHNSON CONTROLSFORM 201.23-EG1 (1007)139
JOHNSON CONTROLS14EVAPYCIV MODELS60Hz 50HzA0267EA/VA 1050(E/V)0287SA/PA 1070(S/P)0287EA/VA 1120(E/V)B0307SA/PA 1180(S/P)0327EA/VA 1220(E/V)0357SA/PA 1
Form 201.23-EG1 (1007)Supersedes: 201.23-EG1 (607)File in ET2
JOHNSON CONTROLSFORM 201.23-EG1 (1007)15
JOHNSON CONTROLS16Standard Efciency Ratings – English - 460V/60HzNOTES:1. kWi = Compressor Input Power2. EER = Chiller EER (includes power fr
JOHNSON CONTROLSFORM 201.23-EG1 (1007)17NOTES:1. kWi = Compressor Input Power2. EER = Chiller EER (includes power from compressors, fans, and c
JOHNSON CONTROLS18Standard Efciency Ratings – English - 460V/60HzNOTES:1. kW = Compressor Input Power2. EER = Chiller EER (includes power fro
JOHNSON CONTROLSFORM 201.23-EG1 (1007)19NOTES:1. kW = Compressor Input Power2. EER = Chiller EER (includes power from compressors, fans, and co
JOHNSON CONTROLS2Introduction ...
JOHNSON CONTROLS20High Efciency Ratings – English - 460V/60Hz AIR TEMPERATURE ON - CONDENSER (°F)LCWT 75.0 80.0 85.0 90.0 95.0 100.0 105.0 110.0 115
JOHNSON CONTROLSFORM 201.23-EG1 (1007)21 AIR TEMPERATURE ON - CONDENSER (°F)LCWT 75.0 80.0 85.0 90.0 95.0 100.0 105.0 110.0 115.0(°F) TONS KW EER TONS
JOHNSON CONTROLS22High Efciency Ratings – English - 460V/60HzNOTES:1. kW = Compressor Input Power2. EER = Chiller EER (includes power from co
JOHNSON CONTROLSFORM 201.23-EG1 (1007)23NOTES:1. kW = Compressor Input Power2. EER = Chiller EER (includes power from compressors, fans, and co
JOHNSON CONTROLS24Standard Efciency Ratings – SI - 460V/60HzMODEL:YCIV0157S/P AIR TEMPERATURE ON - CONDENSER (°C)LCWT 25.0 30.0 35.0 40.0 45.0 46.0(
JOHNSON CONTROLSFORM 201.23-EG1 (1007)25MODEL:YCIV0207S/P AIR TEMPERATURE ON - CONDENSER (°C)LCWT 25.0 30.0 35.0 40.0 45.0 46.0(°C) KWo KWi COP KWo KW
JOHNSON CONTROLS26MODEL:YCIV0267S/P AIR TEMPERATURE ON - CONDENSER (°C)LCWT 25.0 30.0 35.0 40.0 45.0 46.0(°C) KWo KWi COP KWo KWi COP KWo KWi COP KWo
JOHNSON CONTROLSFORM 201.23-EG1 (1007)27MODEL:YCIV0357S/P AIR TEMPERATURE ON - CONDENSER (°C)LCWT 25.0 30.0 35.0 40.0 45.0 46.0(°C) KWo KWi COP KWo KW
JOHNSON CONTROLS28MODEL:YCIV0157E/V AIR TEMPERATURE ON - CONDENSER (°C)LCWT 25.0 30.0 35.0 40.0 45.0 46.0(°C) KWo KWi COP KWo KWi COP KWo KWi COP KWo
JOHNSON CONTROLSFORM 201.23-EG1 (1007)29MODEL:YCIV0197E/V AIR TEMPERATURE ON - CONDENSER (°C)LCWT 25.0 30.0 35.0 40.0 45.0 46.0(°C) KWo KWi COP KWo KW
JOHNSON CONTROLSFORM 201.23-EG1 (1007)3YORK has a proud history of innovation in both compressor design and variable-speed-drive (VSD) technology. Th
JOHNSON CONTROLS30MODEL:YCIV0247E/V AIR TEMPERATURE ON - CONDENSER (°C)LCWT 25.0 30.0 35.0 40.0 45.0 46.0(°C) KWo KWi COP KWo KWi COP KWo KWi COP KWo
JOHNSON CONTROLSFORM 201.23-EG1 (1007)31MODEL:YCIV0327E/V AIR TEMPERATURE ON - CONDENSER (°C)LCWT 25.0 30.0 35.0 40.0 45.0 46.0(°C) KWo KWi COP KWo KW
JOHNSON CONTROLS32Standard Efciency Ratings – SI - 400V/50HzMODEL: YCIV0600S/P AIR TEMPERATURE ON - CONDENSER (°C)LCWT 25.0 30.0 35.0 40.0 45.0 46.0
JOHNSON CONTROLSFORM 201.23-EG1 (1007)33MODEL: YCIV0770S/P AIR TEMPERATURE ON - CONDENSER (°C)LCWT 25.0 30.0 35.0 40.0 45.0 46.0(°C) KWi KWi COP KWi K
JOHNSON CONTROLS34Standard Efciency Ratings – SI - 400V/50HzMODEL: YCIV1000S/P AIR TEMPERATURE ON - CONDENSER (°C)LCWT 25.0 30.0 35.0 40.0 45.0 46.0
JOHNSON CONTROLSFORM 201.23-EG1 (1007)35MODEL: YCIV1340S/P AIR TEMPERATURE ON - CONDENSER (°C)LCWT 25.0 30.0 35.0 40.0 45.0 46.0(°C) KWi KWi COP KWi K
JOHNSON CONTROLS36High Efciency Ratings – SI - 400V/50HzMODEL: YCIV0590E/V AIR TEMPERATURE ON - CONDENSER (°C)LCWT 25.0 30.0 35.0 40.0 45.0 46.0(°C)
JOHNSON CONTROLSFORM 201.23-EG1 (1007)37MODEL: YCIV0760E/V AIR TEMPERATURE ON - CONDENSER (°C)LCWT 25.0 30.0 35.0 40.0 45.0 46.0(°C) KWi KWi COP KWi K
JOHNSON CONTROLS38High Efciency Ratings – SI - 400V/50HzMODEL: YCIV0930E/V AIR TEMPERATURE ON - CONDENSER (°C)LCWT 25.0 30.0 35.0 40.0 45.0 46.0(°C)
JOHNSON CONTROLSFORM 201.23-EG1 (1007)39MODEL: YCIV1220E/V AIR TEMPERATURE ON - CONDENSER (°C)LCWT 25.0 30.0 35.0 40.0 45.0 46.0(°C) KWi KWi COP KWi K
JOHNSON CONTROLS4SpecicationsPOWER AND ELECTRICAL • Johnson Controls has over 25 years of experience designing variable speed drives specic
JOHNSON CONTROLS40Standard Efciency Ratings – English - 380V/60HzMODEL: YCIV0157S/PS_IPLV = 13.4 P_IPLV = 14.7 AIR TEMPERATURE ON - CONDENSER (°F)LC
JOHNSON CONTROLSFORM 201.23-EG1 (1007)41MODEL: YCIV0207S/PS_IPLV = 13.5 P_IPLV = 14.9 AIR TEMPERATURE ON - CONDENSER (°F)LCWT 75.0 80.0 85.0 90.0 95.0
JOHNSON CONTROLS42Standard Efciency Ratings – English - 380V/60HzMODEL: YCIV0267S/PS_IPLV = 12.5 P_IPLV = 15.2 AIR TEMPERATURE ON - CONDENSER (°F)LC
JOHNSON CONTROLSFORM 201.23-EG1 (1007)43NOTES:1. kW = Compressor Input Power2. EER = Chiller EER (includes power from compressors, fans, and co
JOHNSON CONTROLS44High Efciency Ratings – English - 380V/60HzMODEL: YCIV0157E/VE_IPLV = 13.8 V_IPLV = 14.9 AIR TEMPERATURE ON - CONDENSER (°F)LCWT 7
JOHNSON CONTROLSFORM 201.23-EG1 (1007)45MODEL: YCIV0197E/VE_IPLV = 13.1 V_IPLV = 15.2 AIR TEMPERATURE ON - CONDENSER (°F)LCWT 75.0 80.0 85.0 90.0 95.0
JOHNSON CONTROLS46High Efciency Ratings – English - 380V/60HzMODEL: YCIV0247E/VE_IPLV = 13.0 V_IPLV = 15.2 AIR TEMPERATURE ON - CONDENSER (°F)LCWT 7
JOHNSON CONTROLSFORM 201.23-EG1 (1007)47MODEL: YCIV0327E/VE_IPLV = 14.1 V_IPLV = 15.0 AIR TEMPERATURE ON - CONDENSER (°F)LCWT 75.0 80.0 85.0 90.0 95.0
JOHNSON CONTROLS48Standard Efciency Ratings – SI - 380V/60HzMODEL: YCIV0157S/P AIR TEMPERATURE ON - CONDENSER (°C)LCWT 25.0 30.0 35.0 40.0 45.0 46.0
JOHNSON CONTROLSFORM 201.23-EG1 (1007)49MODEL: YCIV0207S/P AIR TEMPERATURE ON - CONDENSER (°C)LCWT 25.0 30.0 35.0 40.0 45.0 46.0(°C) KWi KWi COP KWi K
JOHNSON CONTROLSFORM 201.23-EG1 (1007)5• Discharge line provided with manual compressor shutoff service valve (See Options and Accessories for
JOHNSON CONTROLS50Standard Efciency Ratings – SI - 380V/60HzMODEL: YCIV267S/P AIR TEMPERATURE ON - CONDENSER (°C)LCWT 25.0 30.0 35.0 40.0 45.0 46.0(
JOHNSON CONTROLSFORM 201.23-EG1 (1007)51MODEL: YCIV357S/P AIR TEMPERATURE ON - CONDENSER (°C)LCWT 25.0 30.0 35.0 40.0 45.0 46.0(°C) KWi KWi COP KWi KW
JOHNSON CONTROLS52High Efciency Ratings – SI - 380V/60HzMODEL: YCIV0157E/V AIR TEMPERATURE ON - CONDENSER (°C)LCWT 25.0 30.0 35.0 40.0 45.0 46.0(°C)
JOHNSON CONTROLSFORM 201.23-EG1 (1007)53MODEL: YCIV0197E/V AIR TEMPERATURE ON - CONDENSER (°C)LCWT 25.0 30.0 35.0 40.0 45.0 46.0(°C) KWi KWi COP KWi K
JOHNSON CONTROLS54High Efciency Ratings – SI - 380V/60HzMODEL: YCIV0247E/V AIR TEMPERATURE ON - CONDENSER (°C)LCWT 25.0 30.0 35.0 40.0 45.0 46.0(°C)
JOHNSON CONTROLSFORM 201.23-EG1 (1007)55MODEL: YCIV0327E/V AIR TEMPERATURE ON - CONDENSER (°C)LCWT 25.0 30.0 35.0 40.0 45.0 46.0(°C) KWi KWi COP KWi K
JOHNSON CONTROLS56Contact your nearest Johnson Controls Sales Ofce for weight data.Physical Data (English - Standard Efciency)Refrigerant R-134aSTAN
JOHNSON CONTROLSFORM 201.23-EG1 (1007)57Contact your nearest Johnson Controls Sales Ofce for weight data.Refrigerant R-134aSTANDARD EFFICIENCYMODEL N
JOHNSON CONTROLS58Physical Data (English - High Efciency)Refrigerant R-134aHIGH EFFICIENCYMODEL NUMBER (YCIV____ E/V)General Unit Data60Hz 0157 017
JOHNSON CONTROLSFORM 201.23-EG1 (1007)59Refrigerant R-134aHIGH EFFICIENCYMODEL NUMBER (YCIV____ E/V)General Unit Data60Hz 0267 0287 0327 035750Hz
JOHNSON CONTROLS6and schedule, (variable) out of range, remote input indication, chilled liquid reset setpoint, and history data for la
JOHNSON CONTROLS60Physical Data (SI - Standard Efciency)Refrigerant R-134aSTANDARD EFFICIENCYMODEL NUMBER (YCIV____ S/P)General Unit Data60Hz 0157
JOHNSON CONTROLSFORM 201.23-EG1 (1007)61Refrigerant R-134aSTANDARD EFFICIENCYMODEL NUMBER (YCIV____ S/P)General Unit Data60Hz 0287 0307 0357 03975
JOHNSON CONTROLS62Physical Data (SI - High Efciency)Refrigerant R-134aHIGH EFFICIENCYMODEL NUMBER (YCIV____ E/V)General Unit Data60Hz 0157 0177 01
JOHNSON CONTROLSFORM 201.23-EG1 (1007)63Refrigerant R-134aHIGH EFFICIENCYMODEL NUMBER (YCIV____ E/V)General Unit Data60Hz 0267 0287 0327 035750Hz
JOHNSON CONTROLS64Dimensions – EnglishNotes:1. Placement on a level surface free of obstructions (including snow, for winter operation) or air recircu
JOHNSON CONTROLSFORM 201.23-EG1 (1007)6533 5/16"103 3/8"80"230"101 5/8" 50" 50 5/16" 9 1/8"93 15/16"1 5/1
JOHNSON CONTROLS66Dimensions – English - continuedNotes:1. Placement on a level surface free of obstructions (including snow, for winter operation) or
JOHNSON CONTROLSFORM 201.23-EG1 (1007)67POWER: SINGLE POINT WITH TERMINAL BLOCKXGCYVIEW D-DB33 5/16"103 5/16"A112 13/16"84 1/2"93
JOHNSON CONTROLS68Dimensions – English - continuedModels YCIV0197E/V, YCIV0207S/P, and YCIV0227S/PNotes:1. Placement on a level surface free of obstru
JOHNSON CONTROLSFORM 201.23-EG1 (1007)69POWER: SINGLE POINT WITH TERMINAL BLOCKXGCYVIEW D-D274"33 5/16"103 5/16"88"DC93 15/16"
JOHNSON CONTROLSFORM 201.23-EG1 (1007)7Accessories and Options SOUND REDUCTION OPTIONS – The standard chiller has fans that operate at normal speed, n
JOHNSON CONTROLS70Dimensions – English - continuedModels YCIV0207E/V and YCIV0227E/VNotes:1. Placement on a level surface free of obstructions (includ
JOHNSON CONTROLSFORM 201.23-EG1 (1007)71POWER: SINGLE POINT WITH TERMINAL BLOCKCONTROL PANELVIEW D-D9 1/8"50 5/16"37 13/16"64 3/16"
JOHNSON CONTROLS72Dimensions – English - continuedModels YCIV0247S/P, YCIV0247E/V, and YCIV0267S/PNotes:1. Placement on a level surface free of obstru
JOHNSON CONTROLSFORM 201.23-EG1 (1007)73POWER: SINGLE POINT WITH TERMINAL BLOCKCONTROL PANELVIEW D-D9 1/8"50 5/16"37 13/16"64 3/16"
JOHNSON CONTROLS74Dimensions – English - continuedModels YCIV0267E/V, and YCIV0287S/PNotes:1. Placement on a level surface free of obstructions (inclu
JOHNSON CONTROLSFORM 201.23-EG1 (1007)75POWER: SINGLE POINT WITH TERMINAL BLOCK45 5/16"29 7/8"17 5/8"AAXGCZDD93 15/16"CONTROL PANE
JOHNSON CONTROLS76Dimensions – English - continuedModels YCIV0287E/VNotes:1. Placement on a level surface free of obstructions (including snow, for wi
JOHNSON CONTROLSFORM 201.23-EG1 (1007)77POWER: SINGLE POINT WITH TERMINAL BLOCK50 5/16"50"76"99"19"53 3/8"9 1/8"1 5
JOHNSON CONTROLS78Dimensions – English - continuedModels YCIV0307S/PNotes:1. Placement on a level surface free of obstructions (including snow, for wi
JOHNSON CONTROLSFORM 201.23-EG1 (1007)79POWER: SINGLE POINT WITH TERMINAL BLOCK45 5/16"26 3/8"16 3/16"AAXGCZDD93 15/16"CONTROL PAN
JOHNSON CONTROLS8Accessories and Options (Continued) BUILDING AUTOMATION SYSTEM INTERFACE: • Chiller to accept 4 to 20mA or 0 to 10 VDC input to res
JOHNSON CONTROLS80Dimensions – English - continuedModels YCIV0327E/V and YCIV0357S/PNotes:1. Placement on a level surface free of obstructions (includ
JOHNSON CONTROLSFORM 201.23-EG1 (1007)81POWER: SINGLE POINT WITH TERMINAL BLOCK50 5/16"50"76"99"74 1/8"53 3/8"9 1/8"
JOHNSON CONTROLS82Dimensions – English - continuedModels YCIV0357E/V and YCIV0397S/PNotes:1. Placement on a level surface free of obstructions (includ
JOHNSON CONTROLSFORM 201.23-EG1 (1007)8393 15/16"6 7/8"CONTROL PANELORIGIN53 3/8"9 1/8"50 5/16"50"76"112 11/16"
JOHNSON CONTROLS84Dimensions – SINotes:1. Placement on a level surface free of obstructions (including snow, for winter operation) or air recirculatio
JOHNSON CONTROLSFORM 201.23-EG1 (1007)8584626262032DC58422581 1270 1278 231238733 (TYP)XGCY(3) RIGGING HOLESEACH SIDE (76 X 51)10"WATER OUTLET10&
JOHNSON CONTROLS86Dimensions – SI - continuedNotes:1. Placement on a level surface free of obstructions (including snow, for winter operation) or air
JOHNSON CONTROLSFORM 201.23-EG1 (1007)87DIMENSIONS (mm) UNLESS OTHERWISE NOTEDPOWER: SINGLE POINT WITH TERMINAL BLOCKXGCYVIEW D-DB8462624A286521462387
JOHNSON CONTROLS88Dimensions – SI - continuedNotes:1. Placement on a level surface free of obstructions (including snow, for winter operation) or air
JOHNSON CONTROLSFORM 201.23-EG1 (1007)89POWER: SINGLE POINT WITH TERMINAL BLOCKXGCYVIEW D-D696084626242235DC2387D DXGCZ10" (WATER INLET)10"
JOHNSON CONTROLSFORM 201.23-EG1 (1007)9NOMENCLATUREThe Model Number denotes the following characteristics of the unit:
JOHNSON CONTROLS90Dimensions – SI - continuedNotes:1. Placement on a level surface free of obstructions (including snow, for winter operation) or air
JOHNSON CONTROLSFORM 201.23-EG1 (1007)91POWER: SINGLE POINT WITH TERMINAL BLOCKCONTROL PANELVIEW D-D23112789601631125015248077846235545907236285221741
JOHNSON CONTROLS92Dimensions – SI - continuedNotes:1. Placement on a level surface free of obstructions (including snow, for winter operation) or air
JOHNSON CONTROLSFORM 201.23-EG1 (1007)93POWER: SINGLE POINT WITH TERMINAL BLOCKCONTROL PANELVIEW D-D23112789601631125015248077846235545907236287820091
JOHNSON CONTROLS94Dimensions – SI - continuedNotes:1. Placement on a level surface free of obstructions (including snow, for winter operation) or air
JOHNSON CONTROLSFORM 201.23-EG1 (1007)95POWER: SINGLE POINT WITH TERMINAL BLOCK1151759447AAXGCZDD2387CONTROL PANEL8565502437135846060906884310" (
JOHNSON CONTROLS96Dimensions – SI - continuedNotes:1. Placement on a level surface free of obstructions (including snow, for winter operation) or air
JOHNSON CONTROLSFORM 201.23-EG1 (1007)97POWER: SINGLE POINT WITH TERMINAL BLOCK1278127019302515483135623133 (TYP)1934477592387DDXGCZXGCYCONTROL PANELO
JOHNSON CONTROLS98Dimensions – SI - continuedNotes:1. Placement on a level surface free of obstructions (including snow, for winter operation) or air
JOHNSON CONTROLSFORM 201.23-EG1 (1007)99POWER: SINGLE POINT WITH TERMINAL BLOCK1151671411AAXGCZDD2387CONTROL PANEL8565502438135846060906884310" (