JOHNSON CONTROLS
FORM 102.20-N1 (1109)
2
3. Attach Pipe Chase
a) Set the pipe chase on the pipe chase curb
three inches away from the air handler.
b) Tilt the top of the pipe chase toward the air
handler. Work it under the air handler roof
overhang, being careful not to damage the
neoprene gaskets. Lift the pipe chase slightly
to clear the gasket on the curb and swing the
bottom against the air handler.
c) If there is a baserail, attach the baserail of the
pipe chase to the baserail of the air handler.
Use 3/8" bolts and lock washers provided;
placing bolts through the pipe chase baserail
brackets into the threaded holes in the air
handler baserail (see Fig. 2-43).
d) Make sure the pipe chase is square and the
door(s) close and open without rubbing or
binding.
e) Secure the pipe chase to the top and bottom
raceways (heavy gage metal) of the air
handler through the pre-punched holes of
the inside top and bottom anges of the
pipe chase. Use 1/4"-14 x 1" hex head self-
drilling screws (see Fig. 2-44).
FIG. 2-42 – APPLY GASKET TO PIPE CHASE
3
3
Horizontal gaskets
completely overlap
vertical gaskets in
all four corners
Horizontal gaskets
completely overlap
vertical gaskets in
all four corners
3
Install vertical gaskets first
Install vertical gaskets first
1
Install horizontal
gaskets second
Install horizontal
gaskets second
2
3
3
PIPE CHASE
PIPE CHASE
LD12560A
FIG. 2-43 – PIPE CHASE BASERAIL TO UNIT
BASERAIL INSTALLATION
RIVET NUT
(installed by factory)
BASERAIL COVER
(installed later -
see Fig.2-44)
PIPE CHASE
BASERAIL
UNIT BASERAIL
LOCK WASHER,
(typ.6)
3/8"-16 X 1-1/2" BOLT,
(typ.6)
(When Purchased)
LD12034C
see Fig. 2-51)
Do not over tighten or strip self-drill-
ing screws. Screws in top and bottom
anges go into heavier gauge metal
than screws in cover angles.
f) Check to be sure door closes and latches
properly. If not, loosen self-drilling screws,
re-align pipe chase and re-tighten screws.
Occasionally the curb under the pipe chase
may be uneven, depending on installation.
4. Seal Pipe Chase to Air Handler.
a) Apply caulking to all exterior joints between
pipe chase and air handler baserails (when
purchased) (see Fig. 2-45).
FIG. 2-44 – SCREW PIPE CHASE TOP AND
BOTTOM INTERNAL FLANGES TO AIR
HANDLER
Install with self drilling screws. Insert screws
into, and between, all pre-punched holes in
flange. Typical for both top and bottom
flanges.
PIPE CHASE
Install with self drilling screws. Insert screws
into, and between, all pre-punched holes in
flange. Typical for both top and bottom
flanges.
PIPE CHASE
LD12561A
Vue de la page 60
1 2 ... 56 57 58 59 60 61 62 63 64 65 66 ... 139 140

Commentaires sur ces manuels

Pas de commentaire